2447950000 ACT20P-PRO-FI-AO-DO-P
Brand: Weidmüller
Code: 2447950000
Frequency signal converter, Limit value monitoring, Frequency, PWM, analogue V / mA, Transistor (Alarm)
| Version | Frequency signal converter, Limit value monitoring, Frequency, PWM, analogue V / mA, Transistor (Alarm) |
| Order No. | 2447950000 |
| Type | ACT20P-PRO-FI-AO-DO-P |
| GTIN (EAN) | 4050118462128 |
| Qty. | 1 items |
| 113.7 mm | |
| Depth (inches) | 4.476 inch |
| Height | 117.2 mm |
| Height (inches) | 4.614 inch |
| Width | 12.5 mm |
| Width (inches) | 0.492 inch |
| Net weight | 999 g |
| Storage temperature | -40 °C...85 °C |
| Operating temperature | -40 °C...60 °C |
| Humidity | 0...95 % (no condensation) |
| SIL in compliance with IEC 61508 | None |
| REACH SVHC | Lead 7439-92-1 |
| SCIP | 2f6dd957-421a-46db-a0c2-cf1609156924 |
| Input frequency | 0,01 Hz…200 kHz Treshold current (NAMUR): ≥1.65 mA Hysterisis level: ≥0.2 mA |
| Input voltage | Threshold voltage (NPN / PNP Sensor): 3 V...43.5 V (configurable) Hysterisis level: ≥0.5 V |
| Sensor | NPN/PNP sensor NAMUR sensor, according to EN60947-5-6 Mechanical switch |
| Sensor supply | 18 V ±15 % 8.2 V ±15% (@ NAMUR sensor) |
| Alarm function | configurable Top and bottom limit values, window range Short circuit at input Alarm delay: 0…10 s Hysteresis: 10 V |
| Number of digital outputs | 1 |
| Rated switching current | 100 mA |
| Rated switching voltage | 24 VDC ±30% |
| Type | NPN-Transitor Switching frequency 5 kHz |
| Load resistance current | ≤ 600 Ω |
| Load resistance voltage | > 1 kΩ (60 VAC in <230 vac) > 5 kΩ (24 VAC in <60 VAC) |
| Number of analogue outputs | 1 |
| Output current | -20…+20 mA ± 10mA 0(4)...20 mA |
| Output voltage | 0...5 V 0(1)...5 V 0(2)...10 V -5…+5 V -10...+10 V |
| Signal output | direct or inverted |
| Transmit function | Linear, x1/2, x3/2, x5/2 or user-defined curve (101 points) direct or inverted |
| Type (analogue output) | Voltage and current output (configurable) |
| Accuracy | <±0.1 % of span |
| Configuration | with push-buttons and display |
| Long-term drift | ≤±0.05% of the measurement range / year |
| Power consumption | ≤ 2.6 W |
| Rail | TS 35 |
| Step response time | 40 ms + period |
| Temperature coefficient | ≤ 0.02 % / °C ≤ 100 ppm/K of final value |
| Voltage supply | 24…230 V DC ±15% 24…230 V AC ±15% @48…62 Hz |
| EMC standards | EN 61326-1 |
| Impulse withstand voltage | 5 kV (1.2/50 µs) |
| Insulation voltage | 4 kVeff / 1 min. |
| Pollution severity | 2 |
| Rated voltage | 600 V |
| Surge voltage category | II |
| Safety category | No |
| Type of connection | PUSH IN |
| Approval/Certificate/Document of Conformity | [UL certification](https://mdcop.weidmueller.com/mediadelivery/asset/900_306642) [DNV certification](https://mdcop.weidmueller.com/mediadelivery/asset/900_311428) [Declaration of Conformity](https://mdcop.weidmueller.com/mediadelivery/asset/900_310773) |
| Engineering Data | [CAD data -- STEP](https://mdcop.weidmueller.com/mediadelivery/asset/900_188410) |
| CADENAS eCATALOG | [CAX data](https://weidmueller-embedded.partcommunity.com?catalog=weidmueller_qs&part=2447950000) |
| User Documentation | [Configuration manual](https://mdcop.weidmueller.com/mediadelivery/asset/900_290967) [Instruction sheet](https://mdcop.weidmueller.com/mediadelivery/asset/900_306261) |
| Catalogues | [Catalogues in PDF-format](LINK/Catalog.html) |
| ETIM 6.0 | EC002918 |
| ETIM 7.0 | EC002918 |
| ETIM 8.0 | EC002918 |
| ETIM 9.0 | EC002918 |
| ECLASS 9.0 | 27-21-01-28 |
| ECLASS 9.1 | 27-21-01-28 |
| ECLASS 10.0 | 27-21-01-28 |
| ECLASS 11.0 | 27-21-01-28 |
| ECLASS 12.0 | 27-21-01-28 |
| ECLASS 13.0 | 27-21-01-28 |
| Approvals |    |
| ROHS | Conform |