8581180000 WAS4 PRO FREQ
| Version | Frequency signal isolating transformer, Input : Frequency, Output : I / U |
| Order No. | 8581180000 |
| Type | WAS4 PRO FREQ |
| GTIN (EAN) | 4032248234486 |
| Qty. | 1 items |
| Delivery status | This article will no longer be available in the future. |
| Available until | 31.12.2022 |
| Alternative product | [2447940000](~/p/2447940000) |
| 112.4 mm | |
| Depth (inches) | 4.425 inch |
| Width | 12.5 mm |
| Width (inches) | 0.492 inch |
| Length | 92.4 mm |
| Length (inches) | 3.638 inch |
| Net weight | 118.7 g |
| Storage temperature | -20 °C...85 °C |
| Operating temperature | 0 °C...55 °C |
| SIL in compliance with IEC 61508 | None |
| MTTF | 458 a |
| REACH SVHC | Lead 7439-92-1 |
| SCIP | b25f3b7c-b874-4a4e-a8b2-4f423a7e2a65 |
| Input frequency | 0…100kHz adjustable |
| Number of inputs | 1 |
| Rated input level | Threshold/hysteresis: Namur: approx. 1.7 mA/approx. 0.2 mA; NPN: approx. 6.5 V/approx. 0.2 V; PNP: approx. 6,7 V/approx. 0.5 V |
| Sensor | 2-, 3-wire PNP/NPN, Namur initiator, push-pull step Frequency |
| Sensor supply | 16 V DC @ max. 15 mA |
| Load impedance current | ≤ 600 Ω |
| load impedance voltage | ≥ 1 kΩ |
| Number of outputs | 1 |
| Offset current | max. 100 µA |
| Offset voltage | max. 0.05 V |
| Output current | 0...20 mA 4...20 mA Adjustable |
| Output voltage, note | 0...5 V 0...10 V Adjustable |
| Status indicator | Green LED |
| Output current | 0...20 mA 4...20 mA Adjustable |
| Accuracy | < 0.2% of output range |
| Configuration | DIP switch (measurement range 0...15900 Hz) Frequency generator (measurement range 0...100 kHz) |
| Galvanic isolation | 3-way isolator |
| Power consumption | max. 1.6 W at IOUT = 20 mA |
| Rail | TS 35 |
| Step response time | 360 ms + 2 times the period time of input frequency |
| Temperature coefficient | max. 200 ppm/K of output range |
| Voltage supply | 24 V DC ± 25 % |
| EMC standards | EN 55011 EN 61000-6 EN 61326 |
| Galvanic isolation | 3-way isolator |
| Impulse withstand voltage | 6 kV |
| Insulation voltage | 4 kVeff / 5 s |
| Insulation voltage input or output/rail | 4 kVeff / 1 min. |
| Insulation voltage input or output/supply | 4 kVeff / 5 s |
| Pollution severity | 2 |
| Rated voltage | 300 V |
| Surge voltage category | III |
| Type of connection | Screw connection |
| Stripping length, rated connection | 7 mm |
| Tightening torque, min. | 0.4 Nm |
| Tightening torque, max. | 0.5 Nm |
| Clamping range, rated connection | 2.5 mm² |
| Clamping range, min. | 0.5 mm² |
| Clamping range, max. | 2.5 mm² |
| Product information | This product will soon be replaced by a new product. Please do not use with new systems. Please contact our technical support. |
| Approval/Certificate/Document of Conformity | [Application notes -- Declaration of Conformity](https://mdcop.weidmueller.com/mediadelivery/asset/900_35813) |
| Engineering Data | [CAD data -- STEP](https://mdcop.weidmueller.com/mediadelivery/asset/900_206153) |
| Eplan Data Portal | [Eplan data](https://dataportal.eplan.com/part-details/WEI.8581180000) |
| CADENAS eCATALOG | [CAX data](https://weidmueller-embedded.partcommunity.com?catalog=weidmueller_qs&part=8581180000) |
| WSCAD Universe | [WSCAD data](https://wscaduniverse.com/part-detail?manufacturerId=88&type=0&partNumber=8581180000&norm=0) |
| Software | [Software -- WaveTool.zip](https://mdcop.weidmueller.com/mediadelivery/asset/900_36065) |
| User Documentation | [Device description -- Instruction sheet](https://mdcop.weidmueller.com/mediadelivery/asset/900_35788) |
| Catalogues | [Catalogues in PDF-format](LINK/Catalog.html) |
| ETIM 6.0 | EC002918 |
| ETIM 7.0 | EC002918 |
| ETIM 8.0 | EC002918 |
| ETIM 9.0 | EC002918 |
| ECLASS 9.0 | 27-21-01-28 |
| ECLASS 9.1 | 27-21-01-28 |
| ECLASS 10.0 | 27-21-01-28 |
| ECLASS 11.0 | 27-21-01-28 |
| ECLASS 12.0 | 27-21-01-28 |
| ECLASS 13.0 | 27-21-01-28 |
| Long specification | Measurement isolating transformer for frequency signals, configured with DIP switches
Type WAS4 PRO Freq |
| Short specification | Measurement isolating transformer for frequency signals, configured with DIP switches f/DC measurement isolating transformer in 12.5 mm width, with external power supply: for transmitting, converting and isolating frequencies up to 100 kHz. Namur or 3-wire NPN/PNP sensors can be connected on the input side. Standard DC signals 0(4) to 20 mA/ 0 to 10 V are available on the output side. Internal potentiometer is used for zero and span calibrations. |
| Approvals |    |
| ROHS | Conform |
| UL File Number Search | [UL Website](LINK/UL_search.html) |
| Certificate no. (cULus) | E141197 |
| Certificate no. (cULusEX) | E223527 |
Check out any spare parts and components from the Weidmüller catalog!
Do you want to order a 8581180000 WAS4 PRO FREQ with code: 8581180000?
Leave your request on our website for immediate assistance!