IO-Link converter ICA-AO-I/U-IO-V1
Brand: Pepperl+Fuchs
Code: ICA-AO-I/U-IO-V1
IO-Link converter with analog output (current/voltage)
Datasheet excerpt: Technical data of ICA-AO-I/U-IO-V1
| Product Description |
|---|
| IO-Link converter with analog output (current/voltage) |
| General specifications | ||
|---|---|---|
| UL File Number | E223772 | |
| Functional safety related parameters | ||
| MTTFd | 246 a | |
| Indicators/operating means | ||
| LED 1 | Device status, diagnostics | |
| Electrical specifications | ||
| Rated operating voltage | 18... 30 V | |
| Nominal voltage | 24 V DC | |
| Nominal current | 230 mA | |
| Current consumption | typ. 30 mA | |
| Surge protection | Category II | |
| Interface | ||
| Interface type | IO-Link | |
| IO-Link revision | 1.1 | |
| Device profile | Identification and Diagnosis - I&D | |
| Device ID | 0x0F0502 (984322) | |
| Transfer rate | COM2 (38.4 kBit/s) | |
| Min. cycle time | 2.3 ms | |
| Process data width | 16 bits / 2 bytes | |
| SIO mode support | no | |
| Compatible master port type | A | |
| Output | ||
| Number/Type | 1 analog output for actuators with analog input | |
| Resolution | ADC: 24 bit Process data: 16 bit | |
| Accuracy | 0.1 % FS at 25 °C | |
| Measurement range | Current output or voltage output, configurable: 0 mA…20 mA 4 mA…20 mA 0 V…10 V -10 V…10 V | |
| Sensor supply | 17 … 29.8 V DC ≤ 200 mA | |
| Output filter | Average determination of process data, parameterizable | |
| Temperature influence | 45 ppm/°K | |
| Sampling rate | max. 200 Hz | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61000-6-2:2005, EN 61000-6-4:2007+A1:2011 | |
| Standard conformity | ||
| Degree of protection | EN 60529:2000 | |
| Fieldbus standard | IEC 61131-9 / IO-Link V1.1 | |
| Emitted interference | EN 61000-6-4 | |
| Noise immunity | EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-6 | |
| Shock resistance | EN 60068, Part 2-6, Part 2-27 | |
| Ambient conditions | ||
| Ambient temperature | -30... 70 °C (-22... 158 °F) | |
| Storage temperature | -40... 85 °C (-40... 185 °F) | |
| Relative humidity | max. 85 % | |
| Climatic conditions | Climatic class 3K3 | |
| Altitude | 0... 2000 m | |
| Shock and impact resistance | 50 g, 11 ms, all axes | |
| Pollution degree | 3 | |
| Mechanical specifications | ||
| Degree of protection | IP67 | |
| Connection | IO-Link M12, A-coded Input M12, A-coded | |
| Material | ||
| Contacts | Zinc, CuNi plated | |
| Housing | Plastic PC + PBT | |
| Mass | 44 g | |
| Construction type | Field housing | |
Classifications
| System | Classcode |
|---|---|
| ECLASS 13.0 | 27242601 |
| ECLASS 12.0 | 27242601 |
| ECLASS 11.0 | 27242601 |
| ECLASS 10.0.1 | 27242601 |
| ECLASS 9.0 | 27242601 |
| ECLASS 8.0 | 27242601 |
| ECLASS 5.1 | 27242601 |
| ETIM 9.0 | EC001597 |
| ETIM 8.0 | EC001597 |
| ETIM 7.0 | EC001597 |
| ETIM 6.0 | EC001597 |
| ETIM 5.0 | EC001597 |
| UNSPSC 12.1 | 32151705 |
Check out any spare parts and components from the Pepperl+Fuchs catalog!