Timer, Counter KC-LCD-48-1R-230VAC
Brand: Pepperl+Fuchs
Code: KC-LCD-48-1R-230VAC
Counter/Timer, Adding/subtracting via 2 separate inputs, Batch controller with 1 pre-selection, Easy-to-read, 2-line LCD display with symbols for indicated pre-selection and output status, Display range and preselection range from -999999 up to 999999
Overflow will be evaluated correctly up to 1 decade
Datasheet excerpt: Technical data of KC-LCD-48-1R-230VAC
| Product Description |
|---|
| LCD batch controller with 1 relay output and 230 VAC supply voltage |
| General specifications | ||
|---|---|---|
| Pre-selection | single | |
| Data storage | > 10 years, EEPROM | |
| Programming | keypad-driven menu | |
| Indicators/operating means | ||
| Type | 2-line, 2 x 6-digit LC display with leading sign | |
| Display value | digit height 9 mm | |
| Pre-selection | digit height 7 mm | |
| Key interlock | via "high" potential at "LOCK" input | |
| Decimal point | 0 to max 5 fractional digits | |
| Scale factor | 0.0001... 99.9999 | |
| Reset | manually or external | |
| Electrical specifications | ||
| Fusing | T 0.1 A | |
| Operating voltage | 230 V AC | |
| Power consumption | max. 6.5 VA | |
| Input | ||
| Connection | Counter inputs: A and B Control/reset inputs: LOCK, RESET | |
| Signal voltage | ||
| High | 3.5... 30 V DC | |
| Low | 0... 2 V DC | |
| Counting frequency | 30 Hz / 5 kHz | |
| Minimum pulse duration | Control/reset inputs: static / 1 ms | |
| Impedance | 10 kOhm | |
| Count modes | ||
| Pulse counter | Counting with counting direction (cnt.dir), difference counting (up.dn), up/down counting (quad), | |
| Timer | Time measurement via GATE input (FrErun), counter input A: Start, counter input B: Stop (InpA.InpB.), counter input B: Start/Stop (InpB.InpB.), | |
| Output | ||
| Relay | changeover contact | |
| Switching voltage | max. 250 V AC / 110 V DC | |
| Switching current | max. 3 A AC/DC, min. 30 mA DC, | |
| Switching power | max. 750 VA / 90 W | |
| Mechanical life | 2 x 107 switching cycles | |
| Electrical life | 5 x 104 cycles at 3 A | |
| Response time | < 15 ms pulse counter < 10 ms time counter | |
| Sensor supply | 14.4... 27.6 V DC max. 50 mA at 230 VAC | |
| Compliance with standards and directives | ||
| Directive conformity | ||
| Low Voltage Directive 2006/95/EC | EN 61010-1:2001; protection class: 2 | |
| EMC Directive 2004/108/EC | EN 61000-6-2:2005, EN 50295:1999 | |
| Standard conformity | ||
| Emitted interference | DIN EN 55011:2009, Class B | |
| Mech. capacity | EN 60068-2-6:2008 10 … 55 Hz / 1 mm / XYZ 30 min in each direction | |
| Shock and impact resistance | EN 60068-2-27:1995 100 G / 2 ms / XYZ 3 times in each direction | |
| Ambient conditions | ||
| Ambient temperature | -10... 50 °C (14... 122 °F) | |
| Storage temperature | -25... 75 °C (-13... 167 °F) | |
| Relative humidity | ≤ 93 % at 40 °C (noncondensing) | |
| Altitude | 0... 2000 m | |
| Pollution degree | 2 | |
| Mechanical specifications | ||
| Degree of protection | IP65 (front) | |
| Mass | approx. 230 g | |
| Dimensions | 48 mm x 48 mm x 109.8 mm | |
Classifications
| System | Classcode |
|---|---|
| ECLASS 13.0 | 27210301 |
| ECLASS 12.0 | 27210301 |
| ECLASS 11.0 | 27210301 |
| ECLASS 10.0.1 | 27210301 |
| ECLASS 9.0 | 27210301 |
| ECLASS 8.0 | 27210301 |
| ECLASS 5.1 | 27210301 |
| ETIM 9.0 | EC002300 |
| ETIM 8.0 | EC002300 |
| ETIM 7.0 | EC002300 |
| ETIM 6.0 | EC002300 |
| ETIM 5.0 | EC000677 |
| UNSPSC 12.1 | 41111902 |
Check out any spare parts and components from the Pepperl+Fuchs catalog!
Do you want to order a Timer, Counter KC-LCD-48-1R-230VAC with code: KC-LCD-48-1R-230VAC?
Leave your request on our website for immediate assistance!