Ultrasonic sensor UC500-F65-E8R2-V15
Brand: Pepperl+Fuchs
Code: UC500-F65-E8R2-V15
Level indication , 2 switch outputs, Program input, Series: F65, Rated operating voltage: 24 V DC, Operating voltage: 12... 30 V (including ripple)
In supply voltage interval 12... 20 V sensitivity reduced to 20%... 0%, Output type: 2 switch outputs PNP, NO, UL approval: cULus Listed, General Purpose, CCC approval: CCC approval / marking not required for products rated ≤36 V, Connection type: Connector plug M12 x 1 , 5-pin, Housing: PBT
Datasheet excerpt: Technical data of UC500-F65-E8R2-V15
| General specifications | ||
|---|---|---|
| Sensing range | 60... 500 mm | |
| Adjustment range | 60... 500 mm | |
| Dead band | 0... 60 mm | |
| Standard target plate | 10 mm x 10 mm | |
| Transducer frequency | approx. 300 kHz | |
| Nominal ratings | ||
| Time delay before availability | 250 ms | |
| Limit data | ||
| Permissible cable length | max. 300 m | |
| Indicators/operating means | ||
| LED green | Power on | |
| LED yellow 1 | solid: switching state switch output 1 flashing: misadjustment | |
| LED yellow 2 | solid: switching state switch output 2 flashing: misadjustment | |
| Electrical specifications | ||
| Rated operating voltage | 24 V DC | |
| Operating voltage | 12... 30 V (including ripple) In supply voltage interval 12... 20 V sensitivity reduced to 20%... 0% | |
| Ripple | ≤ 10 % | |
| No-load supply current | ≤ 60 mA | |
| Input | ||
| Input type | 1 program input Teach-In of Smin | |
| Input voltage | ≤ Operating voltage | |
| Level | low level : 0... 3 V (Teach-In active) high level : ≥ 15 V (Teach-In inactive) | |
| Pulse length | ≥ 150 ms | |
| Output | ||
| Output type | 2 switch outputs PNP, NO | |
| Rated operating current | 150 mA , short-circuit/overload protected | |
| Default setting | Switching distance "full", Smax: 80 mm Switching distance "empty", Smin: 450 mm Switching hysteresis "full", HSmax: 20 mm Switching hysteresis "empty", HSmin: 100 mm average value "full", MSmax: 20 average value "empty", MSmin: 110 | |
| Voltage drop | ≤ 3 V | |
| Switch-on delay | 80 ms | |
| Repeat accuracy | ± 0.45 mm | |
| Off-state current | 0.01 mA | |
| Temperature influence | ≤ ± 1.5 % | |
| Compliance with standards and directives | ||
| Standard conformity | ||
| Standards | EN IEC 60947-5-2:2020 IEC 60947-5-2:2019 | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated ≤36 V | |
| Ambient conditions | ||
| Ambient temperature | -25... 70 °C (-13... 158 °F) | |
| Storage temperature | -40... 85 °C (-40... 185 °F) | |
| Shock resistance | 30 g , 11 ms period | |
| Vibration resistance | 10... 55 Hz , Amplitude ± 1 mm | |
| Mechanical specifications | ||
| Connection type | Connector plug M12 x 1 , 5-pin | |
| Degree of protection | IP65 | |
| Material | ||
| Housing | PBT | |
| Transducer | epoxy resin/hollow glass sphere mixture; polyurethane foam | |
| Installation position | any position | |
| Mass | 500 g | |
Classifications
| System | Classcode |
|---|---|
| ECLASS 13.0 | 27272803 |
| ECLASS 12.0 | 27272803 |
| ECLASS 11.0 | 27272803 |
| ECLASS 10.0.1 | 27272803 |
| ECLASS 9.0 | 27272803 |
| ECLASS 8.0 | 27272803 |
| ECLASS 5.1 | 27272803 |
| ETIM 9.0 | EC001849 |
| ETIM 8.0 | EC001849 |
| ETIM 7.0 | EC001849 |
| ETIM 6.0 | EC001849 |
| ETIM 5.0 | EC001849 |
| UNSPSC 12.1 | 41111960 |
Check out any spare parts and components from the Pepperl+Fuchs catalog!