ASi PCB module VAA-4E4A-CB1-Z/E2
Brand: Pepperl+Fuchs
Code: VAA-4E4A-CB1-Z/E2
I/O module as encapsulated PCB with 4 inputs and 4 outputs
Datasheet excerpt: Technical data of VAA-4E4A-CB1-Z/E2
| Product Description |
|---|
| I/O module as encapsulated PCB with 4 inputs and 4 outputs |
| General specifications | ||
|---|---|---|
| Node type | Standard node | |
| AS-Interface specification | V2.0 | |
| Required gateway specification | ≥ V2.0 | |
| UL File Number | E223772 | |
| Electrical specifications | ||
| Rated operating voltage | 26.5... 31.6 V from AS-Interface | |
| Rated operating current | ≤ 30 mA (without sensors) / max. 180 mA | |
| Protection class | III | |
| Surge protection | Ue: Over voltage category III, safe isolated power supplies (PELV) | |
| Input | ||
| Number/Type | 4 inputs for 2- or 3-wire sensors (PNP), DC | |
| Supply | from AS-Interface | |
| Voltage | 21... 31 V | |
| Input current | ≤ 8 mA (limited internally) | |
| Switching point | according to EN 61131-2 Typ 1 | |
| 0 (unattenuated) | ≤ 1.5 mA | |
| 1 (attenuated) | ≥ 4 mA | |
| Output | ||
| Number/Type | 4 electronic outputs, PNP | |
| Supply | from AS-Interface | |
| Voltage | 21... 31 V | |
| Current | ≤ 100 mA per output, ≤ 140 mA total | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 EN 61000-6-4:2007 EN 62026-2:2015 | |
| Standard conformity | ||
| Degree of protection | EN 60529:2000 | |
| Fieldbus standard | EN 62026-2:2013 | |
| Input | EN 61131-2:2015 | |
| Emitted interference | EN 61000-6-4:2007 | |
| AS-Interface | EN 62026-2:2013 | |
| Noise immunity | EN 61326-1:2013 | |
| Programming instructions | ||
| Profile | S-7.0 | |
| IO code | 7 | |
| ID code | 0 | |
| ID1 code | F | |
| ID2 code | E | |
| Data bits (function via AS-Interface) | ||
| D0 | ||
| D1 | ||
| D2 | ||
| D3 | ||
| Parameter bits (programmable via AS-i) | function | |
| P0 | not used | |
| P1 | not used | |
| P2 | not used | |
| P3 | not used | |
| Ambient conditions | ||
| Ambient temperature | -25... 60 °C (-13... 140 °F) | |
| Storage temperature | -40... 85 °C (-40... 185 °F) | |
| Relative humidity | 85 % , noncondensing | |
| Climatic conditions | For indoor use only | |
| Altitude | ≤ 2000 m above MSL | |
| Pollution degree | 2 | |
| Mechanical specifications | ||
| Connection | screw terminals, removable rated connection capacity: rigid/flexible (with and without wire-end ferrules): 0.25 mm2 ... 1.5 mm2 In case of wire end ferrule with plastic sleeve: 0.25 mm2 ... 0.5 mm2 On connection of multiple conductors when using two conductors with the same cross section: Flexible with twin wire end ferrule: | |
| Tightening torque of clamping screws | 0.22... 0.25 Nm | |
Classifications
| System | Classcode |
|---|---|
| ECLASS 13.0 | 27242604 |
| ECLASS 12.0 | 27242604 |
| ECLASS 11.0 | 27242604 |
| ECLASS 10.0.1 | 27242604 |
| ECLASS 9.0 | 27242604 |
| ECLASS 8.0 | 27242604 |
| ECLASS 5.1 | 27242604 |
| ETIM 9.0 | EC001599 |
| ETIM 8.0 | EC001599 |
| ETIM 7.0 | EC001599 |
| ETIM 6.0 | EC001599 |
| ETIM 5.0 | EC001599 |
| UNSPSC 12.1 | 39121535 |
Check out any spare parts and components from the Pepperl+Fuchs catalog!