Datasheet excerpt: Technical data of VBA-4E1A-KE3-ZEJ/SR
| Product Description |
|---|
| KE3 control cabinet module, 4 inputs, 1 control-safe relay output |
| General specifications | ||
|---|---|---|
| Node type | A/B node | |
| AS-Interface specification | V2.1 | |
| Required gateway specification | ≥ V2.1 | |
| UL File Number | E223772 | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 3 | |
| Performance level (PL) | PL e | |
| Indicators/operating means | ||
| LED FAULT | error display; LED red red: communication error | |
| LED PWR | AS-Interface voltage; LED green | |
| LED IN | switching state (input); 4 LED yellow | |
| LED OUT | For flashing patterns see diagnostics table | |
| LED ALARM | PLC reports alarm; red LED | |
| Electrical specifications | ||
| Auxiliary voltage (input) | 12... 30 V DC PELV | |
| Rated operating voltage | 26.5... 31.6 V from AS-Interface | |
| Rated operating current | ≤ 30 mA (without sensors) / max. 200 mA | |
| Protection class | III | |
| Surge protection | UEXT, Ue: Over voltage category III, safe isolated power supplies (PELV) | |
| Input | ||
| Number/Type | 4 inputs for 2- or 3-wire sensors (PNP), DC | |
| Supply | from AS-Interface | |
| Voltage | 21... 31 V DC | |
| Current loading capacity | ≤ 90 mA, overload- and short-circuit proof (INT) | |
| Input current | ≤ 8 mA (limited internally) | |
| Sensor supply | ≤ 90 mA | |
| Switching point | according to DIN EN 61131-2 (Type 2) | |
| 0 (unattenuated) | ≤ 2 mA | |
| 1 (attenuated) | ≥ 4 mA | |
| Signal delay | < 2 ms (input/AS-Interface) | |
| Signal frequency | ≤ 250 Hz | |
| Output | ||
| Number/Type | 1 safety relay output | |
| Supply | from AS-Interface | |
| Nominal load | ||
| Per contact | 3 A / 24 V DC; 3 A / 230 V AC | |
| Usage category | DC-13 and AC-15 | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007 | |
| Standard conformity | ||
| Degree of protection | EN 60529:2000 | |
| Input | EN 61131-2 | |
| Emitted interference | EN 61000-6-4:2007 | |
| AS-Interface | EN 62026-2:2013 | |
| Noise immunity | EN 61000-6-2:2005 EN 62026-2:2013 | |
| Programming instructions | ||
| Profile | S-7.A.E | |
| IO code | 7 | |
| ID code | A | |
| ID1 code | 5 (Can be changed to 7 or F) | |
| ID2 code | E | |
| Data bits (function via AS-Interface) | ||
| D0 | ||
| D1 | ||
| D2 | ||
| D3 | ||
| Parameter bits (programmable via AS-i) | function | |
| P0 | not used | |
| P1 | Output linkage: P1 = 1: safe output switches on release. P1 = 0: safe output switches on release and OUT1=1 | |
| P2 | ID1=5 not used ID1=7 or F P2 = 0 IN3 is input P2 = 1 IN3 notifies of release | |
| P3 | not used | |
| Ambient conditions | ||
| Ambient temperature | 0... 55 °C (32... 131 °F) | |
| Storage temperature | -25... 85 °C (-13... 185 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | removable terminals rated connection capacity: rigid/flexible (with and without wire-end ferrules): 0.25 mm2 ... 2.5 mm2 for multiple-wire connection with two wires of equal cross-section: flexible with twin wire-end ferrules: 0.5 mm2 ... 1.5 mm2 | |
| Material | ||
| Housing | PA 66-FR | |
| Mounting | DIN mounting rail | |
Classifications
| System | Classcode |
|---|---|
| ECLASS 13.0 | 27272603 |
| ECLASS 12.0 | 27242604 |
| ECLASS 11.0 | 27242604 |
| ECLASS 10.0.1 | 27242604 |
| ECLASS 9.0 | 27242604 |
| ECLASS 8.0 | 27242604 |
| ECLASS 5.1 | 27242604 |
| ETIM 9.0 | EC001599 |
| ETIM 8.0 | EC001599 |
| ETIM 7.0 | EC001599 |
| ETIM 6.0 | EC001599 |
| ETIM 5.0 | EC001599 |
| UNSPSC 12.1 | 39121535 |