AS-Interface I/O module VBA-4E3A-G20-ZEL/E2L-P5
Brand: Pepperl+Fuchs
Code: VBA-4E3A-G20-ZEL/E2L-P5
G20 module for digital inputs/outputs, 4 inputs and 3 outputs
Datasheet excerpt: Technical data of VBA-4E3A-G20-ZEL/E2L-P5
| Product Description |
|---|
| G20 module for digital inputs/outputs, 4 inputs and 3 outputs |
| General specifications | ||
|---|---|---|
| Node type | A/B node | |
| AS-Interface specification | V3.0 | |
| Required gateway specification | ≥ V2.1 | |
| Profile | S-7.A.E | |
| IO code | 7 | |
| ID code | A | |
| ID1 code | 7 | |
| ID2 code | E | |
| UL File Number | E223772 "For use in NFPA 79 Applications only" | |
| MTBF | 110 a | |
| Indicators/operating means | ||
| LED FAULT | error display; LED red red: communication error or address is 0 red flashing: overload of sensor power supply or overload of outputs or external auxiliary voltage UAUX missing | |
| LED PWR | AS-Interface voltage; green LED green: voltage OK flashing green: address 0 or overload of sensor power supply or overload of outputs or external auxiliary voltage UAUX missing | |
| LED AUX | ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage | |
| LED IN | switching state (input); 4 LED yellow | |
| LED OUT | Switching state (output); 3 LED yellow | |
| Electrical specifications | ||
| Auxiliary voltage (output) | 20... 30 V DC PELV | |
| Rated operating voltage | 26.5... 31.6 V from AS-Interface | |
| Rated operating current | ≤ 35 mA | |
| Input | ||
| Number/Type | 4 Inputs for 3-wire sensors (PNP), DC | |
| Supply | from external auxiliary voltage UAUX | |
| Current loading capacity | 500 mA , overload and short-circuit protected | |
| Input current | ≤ 8 mA (limited internally) | |
| Switching point | according to DIN EN 61131-2 0 (undamped) ≤ 0.5 mA 1 (damped) ≥ 2.0 mA | |
| Signal delay | < 1 ms (input/AS-Interface) | |
| Output | ||
| Number/Type | 3 electronic outputs, PNP, overload and short-circuit proof | |
| Supply | from external auxiliary voltage UAUX | |
| Voltage | ≥ (UAUX - 0.5 V) | |
| Current | 2 A per output TB ≤ 40 °C: 6 A total TB ≤ 60 °C: OUT1+OUT2 max. 3 A, OUT3 max. 2 A | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 62026-2:2013 | |
| Standard conformity | ||
| Degree of protection | EN 60529:2000 | |
| Fieldbus standard | EN 62026-2:2013 | |
| Input | EN 61131-2:2007 | |
| Emitted interference | EN 61000-6-4:2007 | |
| AS-Interface | EN 62026-2:2013 | |
| Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013 | |
| Ambient conditions | ||
| Ambient temperature | -25... 60 °C (-13... 140 °F) | |
| Storage temperature | -25... 85 °C (-13... 185 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP54 according to EN 60529 | |
| Connection | AS-Interface, AUX: Insulation piercing technology Yellow flat cable/black flat cable Inputs/outputs: M12 round plug connector in accordance with EN 61076-2-101 Inputs: LF type (4-pin, bushing contacts, screw lock, A-coded) Matching connector: LM type or similar Outputs: LF type (4-pin, bushing contacts, screw lock, A-coded) Matching connector: LM type or similar | |
| Mass | 260 g | |
| Mounting | 2 clips with ∅ 8 mm drill hole | |
| Cable length | 2 m | |
| Note | The flat cable routing is designed for 100 actuation cycles | |
Classifications
| System | Classcode |
|---|---|
| ECLASS 13.0 | 27242604 |
| ECLASS 12.0 | 27242604 |
| ECLASS 11.0 | 27242604 |
| ECLASS 10.0.1 | 27242604 |
| ECLASS 9.0 | 27242604 |
| ECLASS 8.0 | 27242604 |
| ECLASS 5.1 | 27242604 |
| ETIM 9.0 | EC001599 |
| ETIM 8.0 | EC001599 |
| ETIM 7.0 | EC001599 |
| ETIM 6.0 | EC001599 |
| ETIM 5.0 | EC001599 |
| UNSPSC 12.1 | 39121535 |
Check out any spare parts and components from the Pepperl+Fuchs catalog!
Do you want to order a AS-Interface I/O module VBA-4E3A-G20-ZEL/E2L-P5 with code: VBA-4E3A-G20-ZEL/E2L-P5?